Burner Control.Configuration Registers.Print
May 17, 2019

Burner Control - BCp.0102.01 - Configuration Registers

Index: all SLATE modules Version: May 17, 2019

0102      Burner Control - BCp.0102.01 - Configuration Registers
Open printable version | Printing help




< > Resize  |  Click below to view:
1 Module number - Module Setup 6 Alert display level - Module Setup 7 Install date - Module Setup 16 Module short name - Module Setup 17 Module name - Module Setup 110 Soft lockout enable - Module Setup 111 Soft lockout power cycle action - Module Setup 112 Hard lockout power cycle action - Module Setup 113 Soft lockout delay time - Module Setup 114 Register demand sources - Module Setup 115 Forced recycle time - Module Setup 116 K1 relay usage - Module Setup 119 Fuel Air control module number - Module Setup 120 Prepurge rate (RPM) - Rate Setup 121 Prepurge rate proving - Rate Setup 122 Lightoff rate (RPM) - Rate Setup 123 Lightoff rate proving - Rate Setup 124 Rate proving delay - Rate Setup 125 Fan speed tolerance - Rate Setup 126 Ignitor duration - Ignition Setup 127 Ignition type - Ignition Setup 128 Flame sensing system type - Ignition Setup 129 Secondary flame sensing time - Ignition Setup 130 Flame failure response time - Flame Module Setup 131 Pilot valve hold enable - Ignition Setup 132 Pilot valve hold transition time - Ignition Setup 133 Manual open switch enable - Ignition Setup 134 Auto ignition enable - Ignition Setup 135 Delayed main valve 2 enable - Ignition Setup 136 Prepurge time - Timings Setup 137 Preignition time - Timings Setup 138 Pilot flame establishing time - Timings Setup 139 Fuel 1 main flame establishing time - Timings Setup 140 Direct burner ignition time - Timings Setup 141 Postpurge time - Timings Setup 142 Fuel selection setup - Interlocks Setup 143 LCI/F1 enable - Interlocks Setup 144 LCI/F2 enable - Interlocks Setup 145 Demand hold limit time - Timings Setup 146 Pre ignition interlock enable - Interlocks Setup 147 ILK start check enable - Interlocks Setup 148 IAS start check enable - Interlocks Setup 149 IAS/LOI monitoring - Interlocks Setup 150 ILK monitoring - Interlocks Setup 151 ILK/IAS proving maximum wait time - Timings Setup 152 Early purge proving delay - Timings Setup 153 Early lightoff proving delay - Timings Setup 154 Purge rate proving failure response - Failure Response Setup 155 Lightoff rate proving failure response - Failure Response Setup 156 Valve proving failure response - Failure Response Setup 157 Pilot ignition failure response - Failure Response Setup 158 Main ignition failure response - Failure Response Setup 159 Run flame failure response - Failure Response Setup 160 LCI open response - Failure Response Setup 161 Demand hold limit response - Failure Response Setup 162 PII open response - Failure Response Setup 163 ILK open response - Failure Response Setup 164 IAS / LOI open response - Failure Response Setup 165 ILK/IAS start check failure response - Failure Response Setup 166 PII dynamic check failure response - Failure Response Setup 167 Dual fuel fault response - Failure Response Setup 168 Flame amplifier fault response - Failure Response Setup 169 MV PV IGN on should be off response - Failure Response Setup 170 MV PV IGN off should be on response - Failure Response Setup 171 Safety relay fault response - Failure Response Setup 172 Flame on should be off response - Failure Response Setup 173 Manual open switch off response - Failure Response Setup 174 Fuel air communication fault response - Failure Response Setup 175 Limit communication fault response - Failure Response Setup 176 Stuck reset switch response - Failure Response Setup 177 Recycle 1 delay time - Recycle Setup 178 Recycle 1 retry limit count - Recycle Setup 179 Recycle 1 retry limit response - Recycle Setup 180 Recycle 2 delay time - Recycle Setup 181 Recycle 2 retry limit count - Recycle Setup 182 Recycle 2 retry limit response - Recycle Setup 183 Recycle 3 delay time - Recycle Setup 184 Recycle 3 retry limit count - Recycle Setup 185 Recycle 3 retry limit response - Recycle Setup 186 Valve proving enable - Valve Proving Setup 187 Valve proving occurrence - Valve Proving Setup 188 Valve proving open time - Valve Proving Setup 189 Valve proving time - Valve Proving Setup 190 Fuel 2 main flame establishing time - Timings Setup 193 Energy saving prepurge - Rate Setup 194 Flame tolerance time - Timings Setup 195 Pilot stabilization time - Timings Setup 600 Socket 1 limit module number - Limit Socket 601 Socket 1 limit name - Limit Socket 602 Socket 1 limit response - Limit Socket 603 Socket 1 limit response trigger - Limit Socket 606 Socket 2 limit module number - Limit Socket 607 Socket 2 limit name - Limit Socket 608 Socket 2 limit response - Limit Socket 609 Socket 2 limit response trigger - Limit Socket 612 Socket 3 limit module number - Limit Socket 613 Socket 3 limit name - Limit Socket 614 Socket 3 limit response - Limit Socket 615 Socket 3 limit response trigger - Limit Socket 618 Socket 4 limit module number - Limit Socket 619 Socket 4 limit name - Limit Socket 620 Socket 4 limit response - Limit Socket 621 Socket 4 limit response trigger - Limit Socket 624 Socket 5 limit module number - Limit Socket 625 Socket 5 limit name - Limit Socket 626 Socket 5 limit response - Limit Socket 627 Socket 5 limit response trigger - Limit Socket 630 Socket 6 limit module number - Limit Socket 631 Socket 6 limit name - Limit Socket 632 Socket 6 limit response - Limit Socket 633 Socket 6 limit response trigger - Limit Socket 636 Socket 7 limit module number - Limit Socket 637 Socket 7 limit name - Limit Socket 638 Socket 7 limit response - Limit Socket 639 Socket 7 limit response trigger - Limit Socket 642 Socket 8 limit module number - Limit Socket 643 Socket 8 limit name - Limit Socket 644 Socket 8 limit response - Limit Socket 645 Socket 8 limit response trigger - Limit Socket 648 Flame amplifier 1 required type - Flame Module Setup 649 Flame amplifier 1 flame threshold - Flame Module Setup 650 Flame amplifier 1 weak flame threshold - Flame Module Setup 655 Flame amplifier 2 required type - Flame Module Setup 656 Flame amplifier 2 flame threshold - Flame Module Setup 657 Flame amplifier 2 weak flame threshold - Flame Module Setup 662 Flame amplifier 3 required type - Flame Module Setup 663 Flame amplifier 3 flame threshold - Flame Module Setup 664 Flame amplifier 3 weak flame threshold - Flame Module Setup 669 Flame amplifier 4 required type - Flame Module Setup 670 Flame amplifier 4 flame threshold - Flame Module Setup 671 Flame amplifier 4 weak flame threshold - Flame Module Setup

1  Module number Category: Module Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
U16

255

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Assigned module number


6  Alert display level Category: Module Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-ubyte
U8

0

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
1
Yes
Yes - Configuration data
No
Yes - Can set up in AX
  Description: Enable/disable alert output (0=Disable, >0=Alert context level)


7  Install date Category: Module Setup
  Units;
DataType:
Max:
Default Value:
Min:
xAX string
String



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
20
Yes
Yes - Configuration data
No
Yes - Can set up in AX
  Description: Date when this module was installed in this system


16  Module short name Category: Module Setup
  Units;
DataType:
Max:
Default Value:
Min:
xAX string
String

Burner

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
10
Yes
Yes - Configuration data
No
Yes - Can set up in AX
  Description: Short module name for Base display use


17  Module name Category: Module Setup
  Units;
DataType:
Max:
Default Value:
Min:
xAX string
String

Burner Control

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
60
Yes
Yes - Configuration data
No
Yes - Can set up in AX
  Description: Full module name for display use


110  Soft lockout enable Category: Module Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Master enable for soft lockouts. If this parameter is value is disable, then all soft lockouts become hard lockouts.
1 Disable Feature is not enabled.
2 Enable Feature is enabled.


111  Soft lockout power cycle action Category: Module Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Action to follow when the control power cycles and it is in a soft lockout condition.
1 Preserved through power cycle Limit status is non-volatile and state retained through power loss
2 Cleared by power cycling Limit status is cleared upon loss of power


112  Hard lockout power cycle action Category: Module Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Action to follow when the control power cycles and it is in a hard lockout condition.
1 Preserved through power cycle Limit status is non-volatile and state retained through power loss
2 Cleared by power cycling Limit status is cleared upon loss of power


113  Soft lockout delay time Category: Module Setup
  Units;
DataType:
Max:
Default Value:
Min:
second
U16
0
60
65535
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
73
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Length of time to delay after a lockout occurs before automatically clearing the lockout and resuming.


114  Register demand sources Category: Module Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
No
Yes - Can set up in AX
  Description: Identifies the registers used to request burner demand.
1 Do not use registers for demand
2 Demand 1 Register
3 Demand 2 Register
4 Demand 1 OR Demand 2 Register


115  Forced recycle time Category: Module Setup
  Units;
DataType:
Max:
Default Value:
Min:
hour
U16
0
0
24
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
71
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Maximum length of time that the burner can continuously run before it is automatically recycled (0 = Disabled).


116  K1 relay usage Category: Module Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: This parameter specifies how the K1 relay will be used. If Wire sheet is chosen then the relay is not used by the burner control and may be controlled by wire sheet logic. If Hot Surface Ignitor is chosen then the relay is closed during the PreIgnition state and throughout the Direct Burner Ignition (DBI) state or Pilot Flame Establishing Period (PFEP), whicheve is enabled. Turning on the Hot Surface Ignitor option disables the IGN output: it remains off. If Blower is chosen then the relay is closed at the start of Prepurge and it remains closed up through the end of Postpurge.
1 Wiresheet Relay is controlled by wiresheet logic.
2 Hot surface ignitor Relay is used for Hot surface ignitor (HSI).
3 Blower Relay is used for blower output.


119  Fuel Air control module number Category: Module Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
U16
0
0
99
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the Fuel/Air control module that interacts with the burner control. 0 = disabled, no such Fuel Air control exists.


120  Prepurge rate (RPM) Category: Rate Setup
  Units;
DataType:
Max:
Default Value:
Min:
revolutions per minute
U16

0

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
104
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: This parameter specifies the rate that will be used for prepurge when this rate is a direct RPM value provided by the burner control. Wire sheet logic may read this value to operate the rate output control. When rate proving is via RPM feedback, the value provided here is the value that is tested vs. the feedback.


121  Prepurge rate proving Category: Rate Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Determines whether and how the modulation rate is proven during prepurge.
1 Disable Prepurge does not need to be proven.
2 PPP switch Prepurge is proven by an input switch.
3 Fuel air control Prepurge is proven by data sent from the Fuel Air ratio control.
4 Fan RPM Prepurge is proven by RPM feedback (e.g., a tachometer input).


122  Lightoff rate (RPM) Category: Rate Setup
  Units;
DataType:
Max:
Default Value:
Min:
revolutions per minute
U16

0

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
104
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: This parameter specifies the rate that will be used for lightoff when this rate is a direct RPM value provided by the burner control. Wire sheet logic may read this value to operate the rate output control. When lightoff rate proving is via RPM feedback, the value provided here is the value that is tested vs. the feedback.


123  Lightoff rate proving Category: Rate Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Determines whether and how the modulation rate is proven during lightoff.
1 Disabled Lightoff does not need to be proven.
2 LPP switch Lightoff position is proven by a switch.
3 Fuel Air control Lightoff is proven by data sent from the Fuel Air control.
4 Fan RPM Lightoff is proven by fan RPM feedback (e.g., via a tachometer).


124  Rate proving delay Category: Rate Setup
  Units;
DataType:
Max:
Default Value:
Min:
second
U16
0
0
300
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
73
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies how long to wait for the modulation rate to be proven before giving up. If 0 is used the rate must be proven immediately. The maximum is 300 seconds (5 minutes).


125  Fan speed tolerance Category: Rate Setup
  Units;
DataType:
Max:
Default Value:
Min:
percent
F32
0
0
100
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
98
4
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: When prepurge and/or lightoff proving is configured to occur depending on measured fan RPM and when the measured speed differs from the specified speed by less than the value provided by this parameter and it has been in this range for 3 seconds, then fan speed is considered to be proven. It then remains proven as long as the speed remains within the tolerance band of this parameter.


126  Ignitor duration Category: Ignition Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: This parameter specifies how long a spark ignitor (IGN output) should be turned on during ignition. If a Hot Surface Ignitor is enabled then IGN must be disabled. Normal duration provides IGN power throughout the Pilot Flame Establishing Period (PFEP) or Direct Burner Ignition (DBI) time, whichever is enabled. Early termination tuns the IGN output off half-way through the PFEP period or one second prior to the end of the DBI time.
1 Disabled, use HSI
2 Normal duration
3 Early spark termination


127  Ignition type Category: Ignition Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Type of ignition system used.
1 Intermittent pilot
2 Interrupted pilot
3 Direct burner ignition


128  Flame sensing system type Category: Ignition Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Describes the number of flame sensors and how they are compared to determine whether successful flame is present.

Valid values:
Single flame sensor
Two flame sensors with OR logic: flame detection is true if either sensor detects flame.
Two flame sensors with AND logic: flame detection is true only if both sensors detect flame
Two flame sensors delayed: the first flame sensor must detect flame within the normal time, then a second sensor must also detect flame after a dleay time expires.
Four flame sensors with OR logic, delayed: same as the previous case, except that each sensor is now paired with another sensor, and within those pairs OR logic is used: a pair detects tht flame is present if either sensor detects flame
Four flame sensors with AND logic, delayed: same as the previous case, except that each sensor in the pair uses AND logic with its partner: each pair detects flame only if both sensors in the pair are sensing a flame.

For delayed options, the delay time (see Secondary flame sensing delay).may be set to zero to mean "no delay" which causes the evaluation to be done immediately. Doing this makes some of the options above equivalent.
1 Single flame sensor Flame is detected using a single flame sensor only.


129  Secondary flame sensing time Category: Ignition Setup
  Units;
DataType:
Max:
Default Value:
Min:
second
U16

0

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
73
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: This parameter specifies the time until the second flame sensor must report a flame when a "delayed" flame detection option is used. The delay time starts at the same time that the non-delayed sensor's time starts, and it is subject to the same pilot test hold. Example: if PFEP is 10 seconds and this parameter's delay time is 18 seconds, then the second sensor must prove flame within 18 seconds after the start of PFEP.


130  Flame failure response time Category: Flame Module Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Maximum length of time between a loss of the sensed flame characteristic (light for optical sensors, current for rectification sensors) and the turn-off of power to the main fuel valves. (The desired response characteristic is to respond as close to this maximum time as possible, without exceeding it, to maximize tolerance of momentary flame signal loss conditions.)
1 Unknown
2 0.8 seconds
3 1 second
4 2 seconds
5 3 seconds


131  Pilot valve hold enable Category: Ignition Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies whether Pilot Valve Hold (PVH) behavior is enabled or not.
1 Disable Feature is not enabled.
2 Enable Feature is enabled.


132  Pilot valve hold transition time Category: Ignition Setup
  Units;
DataType:
Max:
Default Value:
Min:
second
U16
5
5
60
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
73
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: This parameter specifies the timing that occurs to establish the Pilot valve hold condition.


133  Manual open switch enable Category: Ignition Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: This parameter specifies if a manual open switch is to be used. It is a configuration fault if this input and also Direct burner ignition (DBI) is enabled; this feature must be used with a pilot system.

When enabled with a hold for MOS closure: then a hold occurs at the start of MFEP if this input is off. There is no limit to the hold time. During the hold the pilot remains on as normal, and all normal flame monitoring and input monitoring performed during MFEP still occur, however the MFEP timer is held and during this hold the Main Valve outputs are commanded off and monitored to ensure that they are off. As soon as the MOS input is detected as on (including if it is on upon entry to MFEP) then a normal MFEP state occurs: normal MFEP timing begins and proceeds without monitoring of the MOS input.

When enabled with immediate MFEP: No hold occurs and MFEP proceeds normally as if MOS were not used at all.

In both cases, when MOS is enabled in either form: at the end of MFEP and all throughout subsequent states while the main valve is commanded on (e.g. Run Stabilization, Run) a MOS fault response occurs (e.g. a lockout) if the MOS input is detected as off.
1 Disable
2 Enable with MFEP hold for MOS closure
3 Enable with immediate MFEP


134  Auto ignition enable Category: Ignition Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: The auto-ignition feature allows a Limit module to provide indication that the combustion chamber is at or above an autoignition temperature (typically 1400 degrees minimum), and in this case the flame signal from the flame amplifier can be ignored. For this feature to become active one of the limit sockets in the BC must be configured to accept auto-ignition status, and this status must actually be received.
1 Disable Feature is not enabled.
2 Enable Feature is enabled.


135  Delayed main valve 2 enable Category: Ignition Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: If this feature is enabled then MV2 is turned on after flame has been established via MV1 (i.e. upon entry to Run). It is a configuration fault to enable this feature for a fuel that is also enabled for valve proving.
1 Disabled
2 Enable always Enabled for a single fuel or for both fuels in a dual fuel system.
3 Enable for fuel F1
4 Enable for fuel F2


136  Prepurge time Category: Timings Setup
  Units;
DataType:
Max:
Default Value:
Min:
second
U16
0
0
65535
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
73
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Length of time to prepurge the burner to clear out any possible leftover fuel (0=Disable).


137  Preignition time Category: Timings Setup
  Units;
DataType:
Max:
Default Value:
Min:
second
U16
0
0
120
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
73
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: During the pre-ignition state the ignitor is on but neither main valve(s) nor pilot are powered. A time of zero disables the pre-ignition state. This period is typically used either to prove that flame is not simulated by spark, since no flame signal is allowed during pre-ignition, or it is used as pre-heat time for a hot surface ignitor.


138  Pilot flame establishing time Category: Timings Setup
  Units;
DataType:
Max:
Default Value:
Min:
second
U16
0
0
30
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
73
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Length of time allowed before requiring a flame to be present during ignition, when a pilot is used. Ignored if direct burner ignition (DBI) is enabled.


139  Fuel 1 main flame establishing time Category: Timings Setup
  Units;
DataType:
Max:
Default Value:
Min:
second
U16
0
0
30
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
73
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Length of time that an interrupted pilot is on along with the main valve for Fuel 1. At the end of this time an interrupted pilot is turned off and only the main flame provides proof of combustion. (This parameter is ignored for an Intermittent pilot because there is no MFEP, and for Direct burner ignition because DBI time is a separate parameter.)


140  Direct burner ignition time Category: Timings Setup
  Units;
DataType:
Max:
Default Value:
Min:
second
U16
0
0
4
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
73
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Length of time that the main valve may be on before flame must be proven when direct burner ignition is used. This parameter is ignored for other ignition types.


141  Postpurge time Category: Timings Setup
  Units;
DataType:
Max:
Default Value:
Min:
second
U16
0
0
65535
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
73
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Length of time to wait for the burner to clear excess fuel after it has been running or attempted to ignite (0=No postpurge).


142  Fuel selection setup Category: Interlocks Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle
1
1
4
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: If set to "N/A - No Fuel Air module", then the BC does not use Fuel air communication. In this case, if the "Fuel Air Control Module number" parameter is non-zero, then a configuration fault exists and a lockout occurs. A configuration fault lockout also occurs if this parameter has any other value but the "Fuel Air Control Module number" is zero. If a single fuel is selected via "Always use Fuel 1" or "Always use Fuel 2", then the reported fuel selection sent to a Fuel Air control will be according to that selection, no matter how the LCI/F1 and LCI/F2 inputs are used (or not used)..

If "Use Limits LCI/F1 and LCI/F2 to select the fuel" is selected, then both LCI/F1 and LCI/F2 must be configured for Limit functions; it is a configuration fault lockout if they are not. Also in this condition both may be off or one may be on, but a configured response occurs if both are on at the same time (except for a brief transition tolerance of 1 second).
1 N/A - No fuel air module Fuel selection not applicable and is ignored.
2 Always use Fuel 1 Single fuel is selected and will be reported as F1.
3 Always use Fuel 2 Single fuel is selected and will be reported as F2.
4 Use Limits LCI/F1 and LCI/F2 to select the fuel Dual fuel operation is selected via LCI/F1 and LCI/F2.


143  LCI/F1 enable Category: Interlocks Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle
1
1
3
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: When used as Demand, then a call for heat is present when the input is energized and when it is off (and also there is no other source for a call for heat) then the system returns to an idle condition in Standby with no call for heat and no hold condition. (This return to Standby may include going through Postpurge, if the burner was igniting or firing, but eventually it becomes idle.)

When used as a Limit the call for heat comes from some other source and this input must turn on before startup will proceed. During the time when demand is present but LCI is open, a hold is annunciated, describing the reason. An LCI input configured as a limit must remain on throughout the prepurge, ignition, and run states; if it opens during these states, then the startup or run condition is aborted abnormally and a configured response occurs.
1 Disabled The input is disabled and ignored
2 Use as demand The input acts as a demand input, call-for-heat is true when it is on.
3 Use as limit The input acts as a run-permissive input. This selection is required for dual fuel.


144  LCI/F2 enable Category: Interlocks Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle
1
1
3
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: When used as Demand, then a call for heat is present when the input is energized and when it is off (and also there is no other source for a call for heat), then the system returns to an idle condition in Standby with no call for heat and no hold condition. (This return to Standby may include going through Postpurge, if the burner was igniting or firing, but eventually it becomes idle.)

When used as a Limit the call for heat comes from some other source and this input must turn on before startup will proceed. During the time when demand is present but LCI is open, a hold is annunciated, describing the reason. An LCI input configured as a limit must remain on throughout the prepurge, ignition, and run states; if it opens during these states, then the startup or run condition is aborted abnormally and a configured response occurs.
1 Disabled The input is disabled and ignored
2 Use as demand The input acts as a demand input, call-for-heat is true when it is on.
3 Use as limit The input acts as a run-permissive input. This selection is required for dual fuel.


145  Demand hold limit time Category: Timings Setup
  Units;
DataType:
Max:
Default Value:
Min:
second
U16
0
0
65535
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
73
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Maximum time to wait in a Standby hold condition when demand is present. If it fails to resolve for this amount of time, then a configured response occurs. 0= no limit, wait forever.


146  Pre ignition interlock enable Category: Interlocks Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: When "Disabled" the PII input is ignored. When "Enabled with no dynamic check" then the PII input is tested to ensure that it is energized whenever the main valves should be off. Whenever the main valve status changes from 1 or both valves on, to both valves off, then 5 seconds is allowed before checking for the energized state resumes, to give them time to fully close their proof-of-closure switches. If dynamic check is not enabled then the off condition of the PII is never tested, that is, normal operation occurs even if PII is continuously powered at all times. However if the PII input is "Enabled with dynamic check", then during the Run state the PII input must be de-energized. If any testing reveals that the PII is not in its mandated position then a configured response occurs.
1 Disabled PII input is not monitored for any condition.
2 Enabled with no dynamic check PII input is monitored for the On condition, but Off is not checked.
3 Enabled with dynamic check PII input is monitored for both the On and Off conditions.


147  ILK start check enable Category: Interlocks Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies whether the interlock (ILK) input must be off at startup as a check that proves it is possible for it to signal the off condition. If ILK is on, the control waits for it to turn off before startup is allowed. If it fails to turn off for 4 minutes then a configured response occurs.
1 Disable Feature is not enabled.
2 Enable Feature is enabled.


148  IAS start check enable Category: Interlocks Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies whether the interrupted air switch (IAS) input must be off at startup as a check that proves it is possible for it to signal the off condition. If IAS is on, the control waits for it to turn off before startup is allowed. If it fails to turn off for 4 minutes then a configured response occurs.
1 Disable Feature is not enabled.
2 Enable Feature is enabled.


149  IAS/LOI monitoring Category: Interlocks Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: This input can be configured as either an interrupted air switch or a lockout input (primarily used in EC applications). When monitored as an IAS input then during Prepurge it is not a fault for the input to be off until the "Airflow proving maximum wait time" has elapsed. The measured purge timing does not begin until the IAS is energized. If configured as a LOI input then it must be energized at all times, except that during initialization it is given time to turn on. If the input is in an incorrect state then a configured response occurs.
1 Disable IAS and LOI are not monitored.
2 IAS: Prepurge only IAS is monitored during prepurge only.
3 IAS: Prepurge/Ignition IAS is monitored during prepurge and ignition.
4 LOI: At all times including Standby LOI is monitored at all times.


150  ILK monitoring Category: Interlocks Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies when the interlock (ILK) string is monitored by the control. This input can be configured as either an a normal interlock input or a lockout input (as is typically used in EC applications). When monitored as a normal interlock input then during Prepurge it is not a fault for the input to be off until the "Airflow proving maximum wait time" has elapsed. The measured purge timing does not begin until the ILK input is energized. If configured as a LOI input then it must be energized at all times, except that during initialization it is given time to turn on. If the input is in an incorrect state then a configured response occurs.
1 LOI: At all times including Standby Use this input as a lockout input, such that if it ever turns off a configured response (such as a lockout) occurs.
2 During Prepurge, Ignition, and Run Use the input as a normal interlock input, where the "Airflow proving maximum wait time" is used as a tolerance time during Prepurge.


151  ILK/IAS proving maximum wait time Category: Timings Setup
  Units;
DataType:
Max:
Default Value:
Min:
second
U16
0
0
60
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
73
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: This parameter provides the time that a de-energized ILK (or IAS, whichever is configured) is tolerated measured from the start of the prepurge state. (In previous controls this time was fixed; however in this system it is programmable to accomodate VFDs which take a longer time to provide airflow.) If this time is exceeded without establishing the monitored input as energized, then a configured response occurs.


152  Early purge proving delay Category: Timings Setup
  Units;
DataType:
Max:
Default Value:
Min:
second
U16
0
30
65535
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
73
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: If purge proving is enabled and it is proven immediately upon entry to the prepurge state, then an extra delay occurs that lasts for the duration defined by this parameter. 0=accept the proven condition with no delay.


153  Early lightoff proving delay Category: Timings Setup
  Units;
DataType:
Max:
Default Value:
Min:
second
U16
0
30
65535
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
73
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: If lightoff proving is enabled and it is proven immediately upon entry to the drive-to-lightoff state, then an extra delay occurs that lasts for the duration defined by this parameter. 0=accept the proven condition with no delay.


154  Purge rate proving failure response Category: Failure Response Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the action to take in response to a failure to achieve the target firing rate during purge within the time provided by the "Rate proving delay" parameter.
1 Unknown No specific response is determined for this failure.
2 Recycle 1 Failure should perform a type 1 recycle response.
3 Recycle 2 Failure should perform a type 2 recycle response.
4 Recycle 3 Failure should perform a type 3 recycle response.
5 Soft lockout Failure should perform a soft lockout.
6 Hard lockout Failure should perform a hard lockout.


155  Lightoff rate proving failure response Category: Failure Response Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the action to take in response to a failure to achieve the target firing rate during lightoff within the time provided by the "Rate proving delay" parameter.
1 Unknown No specific response is determined for this failure.
2 Recycle 1 Failure should perform a type 1 recycle response.
3 Recycle 2 Failure should perform a type 2 recycle response.
4 Recycle 3 Failure should perform a type 3 recycle response.
5 Soft lockout Failure should perform a soft lockout.
6 Hard lockout Failure should perform a hard lockout.


156  Valve proving failure response Category: Failure Response Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the action to take in response to a failure to prove that the valve is functioning properly during the valve proving test.
1 Unknown No specific response is determined for this failure.
2 Recycle 1 Failure should perform a type 1 recycle response.
3 Recycle 2 Failure should perform a type 2 recycle response.
4 Recycle 3 Failure should perform a type 3 recycle response.
5 Soft lockout Failure should perform a soft lockout.
6 Hard lockout Failure should perform a hard lockout.


157  Pilot ignition failure response Category: Failure Response Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the action to take in response when the pilot fails to ignite.
1 Unknown No specific response is determined for this failure.
2 Recycle 1 Failure should perform a type 1 recycle response.
3 Recycle 2 Failure should perform a type 2 recycle response.
4 Recycle 3 Failure should perform a type 3 recycle response.
5 Soft lockout Failure should perform a soft lockout.
6 Hard lockout Failure should perform a hard lockout.


158  Main ignition failure response Category: Failure Response Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the action to take in response when a satisfactory main flame is not established during ignition. This response is used for flame failure during DBI, MFEP, and during the first 10 seconds of the Run state.
1 Unknown No specific response is determined for this failure.
2 Recycle 1 Failure should perform a type 1 recycle response.
3 Recycle 2 Failure should perform a type 2 recycle response.
4 Recycle 3 Failure should perform a type 3 recycle response.
5 Soft lockout Failure should perform a soft lockout.
6 Hard lockout Failure should perform a hard lockout.


159  Run flame failure response Category: Failure Response Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the action to take in response to a loss of satisfactory flame after the burner has entered the Run state. This response is used for flame failures that occur after the first 10 seconds of the Run state. Prior to this, during DBI, MFEP, or the first 10 seconds of Run, the Ignition flame failure response is used.
1 Unknown No specific response is determined for this failure.
2 Recycle 1 Failure should perform a type 1 recycle response.
3 Recycle 2 Failure should perform a type 2 recycle response.
4 Recycle 3 Failure should perform a type 3 recycle response.
5 Soft lockout Failure should perform a soft lockout.
6 Hard lockout Failure should perform a hard lockout.


160  LCI open response Category: Failure Response Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Only when LCI/F1 or LCI/F2 is defined as a Limit input, then this parameter identifies the action to take in response to LCI opening abnormally while it should be closed during the burner sequence. Does not apply if LCI/F1 or LCI/F2 is defined as a Demand input, because then its opening during a sequence is a normal indication of the end of demand.
1 Unknown No specific response is determined for this failure.
2 Recycle 1 Failure should perform a type 1 recycle response.
3 Recycle 2 Failure should perform a type 2 recycle response.
4 Recycle 3 Failure should perform a type 3 recycle response.
5 Soft lockout Failure should perform a soft lockout.
6 Hard lockout Failure should perform a hard lockout.


161  Demand hold limit response Category: Failure Response Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the action to take in response to exceeding the "Demand hold limit time" when there is a call for heat.
1 Unknown No specific response is determined for this failure.
2 Recycle 1 Failure should perform a type 1 recycle response.
3 Recycle 2 Failure should perform a type 2 recycle response.
4 Recycle 3 Failure should perform a type 3 recycle response.
5 Soft lockout Failure should perform a soft lockout.
6 Hard lockout Failure should perform a hard lockout.


162  PII open response Category: Failure Response Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the action to take in response to PII being open when it should be closed during the burner sequence.
1 Unknown No specific response is determined for this failure.
2 Recycle 1 Failure should perform a type 1 recycle response.
3 Recycle 2 Failure should perform a type 2 recycle response.
4 Recycle 3 Failure should perform a type 3 recycle response.
5 Soft lockout Failure should perform a soft lockout.
6 Hard lockout Failure should perform a hard lockout.


163  ILK open response Category: Failure Response Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the action to take in response to ILK being open when it should be closed during the burner sequence.
1 Unknown No specific response is determined for this failure.
2 Recycle 1 Failure should perform a type 1 recycle response.
3 Recycle 2 Failure should perform a type 2 recycle response.
4 Recycle 3 Failure should perform a type 3 recycle response.
5 Soft lockout Failure should perform a soft lockout.
6 Hard lockout Failure should perform a hard lockout.


164  IAS / LOI open response Category: Failure Response Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the action to take in response to Interrupted Air Switch being open when it should be closed during the burner sequence.
1 Unknown No specific response is determined for this failure.
2 Recycle 1 Failure should perform a type 1 recycle response.
3 Recycle 2 Failure should perform a type 2 recycle response.
4 Recycle 3 Failure should perform a type 3 recycle response.
5 Soft lockout Failure should perform a soft lockout.
6 Hard lockout Failure should perform a hard lockout.


165  ILK/IAS start check failure response Category: Failure Response Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the action to take in response to a failure of the start check for the ILK and/or IAS inputs.
1 Unknown No specific response is determined for this failure.
2 Recycle 1 Failure should perform a type 1 recycle response.
3 Recycle 2 Failure should perform a type 2 recycle response.
4 Recycle 3 Failure should perform a type 3 recycle response.
5 Soft lockout Failure should perform a soft lockout.
6 Hard lockout Failure should perform a hard lockout.


166  PII dynamic check failure response Category: Failure Response Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the action to take in response to a failure of the dynamic check of the PII input to ensure that it signals the Off condition during Run.
1 Unknown No specific response is determined for this failure.
2 Recycle 1 Failure should perform a type 1 recycle response.
3 Recycle 2 Failure should perform a type 2 recycle response.
4 Recycle 3 Failure should perform a type 3 recycle response.
5 Soft lockout Failure should perform a soft lockout.
6 Hard lockout Failure should perform a hard lockout.


167  Dual fuel fault response Category: Failure Response Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the action to take in response to both LCI/F1 and LCI/F2 being energized (an invalid condition) when dual fuel is enabled.
1 Unknown No specific response is determined for this failure.
2 Recycle 1 Failure should perform a type 1 recycle response.
3 Recycle 2 Failure should perform a type 2 recycle response.
4 Recycle 3 Failure should perform a type 3 recycle response.
5 Soft lockout Failure should perform a soft lockout.
6 Hard lockout Failure should perform a hard lockout.


168  Flame amplifier fault response Category: Failure Response Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the action to take in response to a failure in the flame detector system.
1 Unknown No specific response is determined for this failure.
2 Recycle 1 Failure should perform a type 1 recycle response.
3 Recycle 2 Failure should perform a type 2 recycle response.
4 Recycle 3 Failure should perform a type 3 recycle response.
5 Soft lockout Failure should perform a soft lockout.
6 Hard lockout Failure should perform a hard lockout.


169  MV PV IGN on should be off response Category: Failure Response Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the action to take if an input is on when it should be off (e.g. its shorted to power).
1 Unknown No specific response is determined for this failure.
2 Recycle 1 Failure should perform a type 1 recycle response.
3 Recycle 2 Failure should perform a type 2 recycle response.
4 Recycle 3 Failure should perform a type 3 recycle response.
5 Soft lockout Failure should perform a soft lockout.
6 Hard lockout Failure should perform a hard lockout.


170  MV PV IGN off should be on response Category: Failure Response Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the action to take in response to an input that should be powered but is not (internal fault).
1 Unknown No specific response is determined for this failure.
2 Recycle 1 Failure should perform a type 1 recycle response.
3 Recycle 2 Failure should perform a type 2 recycle response.
4 Recycle 3 Failure should perform a type 3 recycle response.
5 Soft lockout Failure should perform a soft lockout.
6 Hard lockout Failure should perform a hard lockout.


171  Safety relay fault response Category: Failure Response Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the action to take if the safety relay is in the wrong state (internal fault).
1 Unknown No specific response is determined for this failure.
2 Recycle 1 Failure should perform a type 1 recycle response.
3 Recycle 2 Failure should perform a type 2 recycle response.
4 Recycle 3 Failure should perform a type 3 recycle response.
5 Soft lockout Failure should perform a soft lockout.
6 Hard lockout Failure should perform a hard lockout.


172  Flame on should be off response Category: Failure Response Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the action to take in when the flame is on when it should be off in any state.
1 Unknown No specific response is determined for this failure.
2 Recycle 1 Failure should perform a type 1 recycle response.
3 Recycle 2 Failure should perform a type 2 recycle response.
4 Recycle 3 Failure should perform a type 3 recycle response.
5 Soft lockout Failure should perform a soft lockout.
6 Hard lockout Failure should perform a hard lockout.


173  Manual open switch off response Category: Failure Response Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the action to take if the Manual Open Switch is off when it should be on (during MFEP and Run).
1 Unknown No specific response is determined for this failure.
2 Recycle 1 Failure should perform a type 1 recycle response.
3 Recycle 2 Failure should perform a type 2 recycle response.
4 Recycle 3 Failure should perform a type 3 recycle response.
5 Soft lockout Failure should perform a soft lockout.
6 Hard lockout Failure should perform a hard lockout.


174  Fuel air communication fault response Category: Failure Response Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the action to take if the fuel air control does not have reliable communication with the burner control that is its partner.
1 Unknown No specific response is determined for this failure.
2 Recycle 1 Failure should perform a type 1 recycle response.
3 Recycle 2 Failure should perform a type 2 recycle response.
4 Recycle 3 Failure should perform a type 3 recycle response.
5 Soft lockout Failure should perform a soft lockout.
6 Hard lockout Failure should perform a hard lockout.


175  Limit communication fault response Category: Failure Response Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the action to take in response to a failure in communication between the burner control and a limit module that is specified by the burner control to interact with the burner control.
1 Unknown No specific response is determined for this failure.
2 Recycle 1 Failure should perform a type 1 recycle response.
3 Recycle 2 Failure should perform a type 2 recycle response.
4 Recycle 3 Failure should perform a type 3 recycle response.
5 Soft lockout Failure should perform a soft lockout.
6 Hard lockout Failure should perform a hard lockout.


176  Stuck reset switch response Category: Failure Response Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the action to take if the Reset pushbutton is stuck.
1 Unknown No specific response is determined for this failure.
2 Recycle 1 Failure should perform a type 1 recycle response.
3 Recycle 2 Failure should perform a type 2 recycle response.
4 Recycle 3 Failure should perform a type 3 recycle response.
5 Soft lockout Failure should perform a soft lockout.
6 Hard lockout Failure should perform a hard lockout.


177  Recycle 1 delay time Category: Recycle Setup
  Units;
DataType:
Max:
Default Value:
Min:
second
U16
5
5
65535
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
73
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the delay time that must take place while in Standby before retrying the burner sequence for the first recycle handler. The 5 second minimum ensures that the recycle reason has time to be displayed.


178  Recycle 1 retry limit count Category: Recycle Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
U16
0
3
65534
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Maximum number of recycle retries before giving up for the first recycle handler. Retry counting is cleared when the burner reaches the Run state or when call for heat disappears.


179  Recycle 1 retry limit response Category: Recycle Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the action to take in response to the number of recycles hitting the retry limit for the first recycle handler. When the response is "None" the recycles continue forever until successful or demand is no longer requested.
1 None
2 Soft lockout
3 Hard lockout


180  Recycle 2 delay time Category: Recycle Setup
  Units;
DataType:
Max:
Default Value:
Min:
second
U16
5
5
65535
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
73
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the delay time that must take place while in Standby before retrying the burner sequence for the second recycle handler. The 5 second minimum ensures that the recycle reason has time to be displayed.


181  Recycle 2 retry limit count Category: Recycle Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
U16
0
3
65534
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Maximum number of recycle retries before giving up for the second recycle handler. Retry counting is cleared when the burner reaches the Run state or when call for heat disappears.


182  Recycle 2 retry limit response Category: Recycle Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the action to take in response to the number of recycles hitting the retry limit for the second recycle handler. When the response is "None" the recycles continue forever until successful or demand is no longer requested.
1 None
2 Soft lockout
3 Hard lockout


183  Recycle 3 delay time Category: Recycle Setup
  Units;
DataType:
Max:
Default Value:
Min:
second
U16
5
5
65535
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
73
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the delay time that must take place while in Standby before retrying the burner sequence for the third recycle handler. The 5 second minimum ensures that the recycle reason has time to be displayed.


184  Recycle 3 retry limit count Category: Recycle Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
U16
0
3
65534
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Maximum number of recycle retries before giving up for the third recycle handler. Retry counting is cleared when the burner reaches the Run state or when call for heat disappears.


185  Recycle 3 retry limit response Category: Recycle Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Identifies the action to take in response to the number of recycles hitting the retry limit for the third recycle handler. When the response is "None" the recycles continue forever until successful or demand is no longer requested.
1 None
2 Soft lockout
3 Hard lockout


186  Valve proving enable Category: Valve Proving Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle
1
1
4
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: If this feature is enabled, then valve proving is performed when the configured fuel is selected. It is a configuration fault to enable this feature for a fuel that is also enabled to use a delayed main valve.

"Enable always" causes valve proving to be performed always, either for a single fuel or for both fuels in a dual fuel system. "Enable for dual fuel LCI/F1" and "Enable for dual fuel LCI/F2" are allowed only if the "Fuel selection setup" parameter enables dual fuels; otherwise a configuration fault occurs.
1 Disabled Valve proving is not enabled.
2 Enabled always Turns on valve proving for a single fuel, or for both fuels in a dual fuel system.
3 Enabled for dual fuel selected by LCI/F1 Turns on valve proving for dual fuel when LCI/F1 is selected.
4 Enabled for dual fuel selected by LCI/F2 Turns on valve proving for dual fuel when LCI/F2 is selected.


187  Valve proving occurrence Category: Valve Proving Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Determines when valve proving occurs if it is enabled. Valve proving includes two tests: one where the short pipe between the two shutoff valves is pressurized (high pressure test) and one where it is depressurized (low pressure test.

The Before and After options both perform both of these parts together, one after the other. Valve proving Before runs simultaneously with Prepurge and will delay lightoff if it lasts longer than Prepurge. Valve proving After run simultaneously with Postpurge (if any) and will delay re-entry to the Standby state until it is done, if it lasts longer than Postpurge. The Both option is the same as selecting both of those.

The Split option performs the high pressure test before Run (simultaneous with Prepurge) and the low pressure test after Run (simultaneous with Postpurge). This has the advantage of reducing valve cycling and avoiding the emission of a small amount of unburned fuel.
1 Before Run Both pressure tests BEFORE entering the Run state only.
2 After Run Both pressure tests AFTER in the Run state only.
3 Both before and after Run Both pressure tests before and after entering the Run state.
4 Split High pressure test before Run and low pressure test after Run.


188  Valve proving open time Category: Valve Proving Setup
  Units;
DataType:
Max:
Default Value:
Min:
second
U16
0
5
60
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
73
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Determines how long one valve is commanded to be open to pressurize or depressurize the pipe between the two shutoff valves. A typical value is 5 seconds for a slow valve; shorter times may be used for faster valves.


189  Valve proving time Category: Valve Proving Setup
  Units;
DataType:
Max:
Default Value:
Min:
second
U16
0
0
65535
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
73
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Test time needed to prove that valve leakage is acceptable during a valve proving test.


190  Fuel 2 main flame establishing time Category: Timings Setup
  Units;
DataType:
Max:
Default Value:
Min:
second
U16
0
0
30
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
73
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Length of time that an interrupted pilot is on along with the main valve for Fuel 2. At the end of this time an interrupted pilot is turned off and only the main flame provides proof of combustion. (This parameter is ignored for an Intermittent pilot because there is no MFEP, and for Direct burner ignition because DBI time is a separate parameter.)


193  Energy saving prepurge Category: Rate Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle
1
1
2
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Delay blower relay turn-on until the prepurge rate is proven as long as certain conditions are met: K1 is configured as the Blower, prepurge time is non-zero, and prepurge proving is PPP switch or Fuel Air control.
1 Disable Feature is not enabled.
2 Enable Feature is enabled.


194  Flame tolerance time Category: Timings Setup
  Units;
DataType:
Max:
Default Value:
Min:
second
U16
0
240
65535
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
73
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Length of time allowed for flame to be present while in the Initiate and Standby states before faulting.


195  Pilot stabilization time Category: Timings Setup
  Units;
DataType:
Max:
Default Value:
Min:
second
U16
0
0
65535
Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
73
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Length of time allowed for pilot flame to stabilize.


600  Socket 1 limit module number Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
U16



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Module number of the Limit module that is providing data for socket "N". No other Limit module will be examined for a safety package for this socket.


601  Socket 1 limit name Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
xAX string
String



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
12
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: String up to 12 characters (8 bit) that provide a unique name for the socket. All sockets in a burner control must have different names. When a safety packet is received from the module identified by the "Socket N limit module number" register, and when this packet is correct as defined by the SLATE "SafetyDataPackets" document, and when the name provided by this parameter matches the name provided in the packet, then the status data provided by the limit block is used as valid data. A safety packet having a name which does not match any of the sockets (and also the socket's module number) is ignored.


602  Socket 1 limit response Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Response to valid (as defined by other socket configuration registers) limit block status values. The responses below are suppressed during those states when it is not desired, as specified by the value of the "Socket N limit respond when" parameter.

If the response is set to "Recycle 1", "Recycle 2", or "Recycle 3" then, whenever the limit block status is not "Limit OK" then a recycle and hold occurs until the status reverts to "Limit OK"

If the response is set to "Soft lockout" or "Hard lockout" then, whenever the limit block status is not "Limit OK" then the appropriate type of lockout occurs.

If the response is set to "Auto-ignition active" then whenever the limit block status is "Auto ignition threshold exceeded" then the BC, when configured for auto-ignition detection, will act as defined by the "Auto ignition enable" parameter. For this response, the "Socket N response when" parameter value is ignored.

If the "Auto ignition threshold exceeded" status is received but this parameter is not configured for "Auto-ignition active" then this status is ignored.
1 Unknown It is not specified what should happen for an invalid limit event.
2 Recycle 1 Invalid limit event should cause a type 1 recycle to occur.
3 Recycle 2 Invalid limit event should cause a type 2 recycle to occur.
4 Recycle 3 Invalid limit event should cause a type 3 recycle to occur.
5 Soft lockout Invalid limit event should cause a soft lockout to occur.
6 Hard lockout Invalid limit event should cause a hard lockout to occur.
7 Auto-ignition active Operate according to auto-ignition conditions having been met.


603  Socket 1 limit response trigger Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: When the burner control responds to the limit. It also provides a master-disable for the socket. The values are:
Disable - this limit socket is inactive
Always - this limit socket is active without regard to BC state
Prepurge and Ignition and Run - this limit socket is active during the named states (and their substates)
Ignition and Run - this limit socket is active during the named states (and their substates)
Flame is on - this limit socket is active whenever flame is required to be on
Run - this limit socket is active during the BC's Run state (and its substates, if any).
1 Disabled - Ignore limit Limit socket is inactive.
2 Always Check limit in all states.
3 Prepurge, Ignition and Run Only check limit when in prepurge, ignition, or Run states.
4 Ignition and Run Only check limit when in ignition or Run states.
5 Flame is on Only check limit when flame is present.
6 Run Only check limit when in Run state.


606  Socket 2 limit module number Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
U16



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Module number of the Limit module that is providing data for socket "N". No other Limit module will be examined for a safety package for this socket.


607  Socket 2 limit name Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
xAX string
String



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
12
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: String up to 12 characters (8 bit) that provide a unique name for the socket. All sockets in a burner control must have different names. When a safety packet is received from the module identified by the "Socket N limit module number" register, and when this packet is correct as defined by the SLATE "SafetyDataPackets" document, and when the name provided by this parameter matches the name provided in the packet, then the status data provided by the limit block is used as valid data. A safety packet having a name which does not match any of the sockets (and also the socket's module number) is ignored.


608  Socket 2 limit response Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Response to valid (as defined by other socket configuration registers) limit block status values. The responses below are suppressed during those states when it is not desired, as specified by the value of the "Socket N limit respond when" parameter.

If the response is set to "Recycle 1", "Recycle 2", or "Recycle 3" then, whenever the limit block status is not "Limit OK" then a recycle and hold occurs until the status reverts to "Limit OK"

If the response is set to "Soft lockout" or "Hard lockout" then, whenever the limit block status is not "Limit OK" then the appropriate type of lockout occurs.

If the response is set to "Auto-ignition active" then whenever the limit block status is "Auto ignition threshold exceeded" then the BC, when configured for auto-ignition detection, will act as defined by the "Auto ignition enable" parameter. For this response, the "Socket N response when" parameter value is ignored.

If the "Auto ignition threshold exceeded" status is received but this parameter is not configured for "Auto-ignition active" then this status is ignored.
1 Unknown It is not specified what should happen for an invalid limit event.
2 Recycle 1 Invalid limit event should cause a type 1 recycle to occur.
3 Recycle 2 Invalid limit event should cause a type 2 recycle to occur.
4 Recycle 3 Invalid limit event should cause a type 3 recycle to occur.
5 Soft lockout Invalid limit event should cause a soft lockout to occur.
6 Hard lockout Invalid limit event should cause a hard lockout to occur.
7 Auto-ignition active Operate according to auto-ignition conditions having been met.


609  Socket 2 limit response trigger Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: When the burner control responds to the limit. It also provides a master-disable for the socket. The values are:
Disable - this limit socket is inactive
Always - this limit socket is active without regard to BC state
Prepurge and Ignition and Run - this limit socket is active during the named states (and their substates)
Ignition and Run - this limit socket is active during the named states (and their substates)
Flame is on - this limit socket is active whenever flame is required to be on
Run - this limit socket is active during the BC's Run state (and its substates, if any).
1 Disabled - Ignore limit Limit socket is inactive.
2 Always Check limit in all states.
3 Prepurge, Ignition and Run Only check limit when in prepurge, ignition, or Run states.
4 Ignition and Run Only check limit when in ignition or Run states.
5 Flame is on Only check limit when flame is present.
6 Run Only check limit when in Run state.


612  Socket 3 limit module number Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
U16



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Module number of the Limit module that is providing data for socket "N". No other Limit module will be examined for a safety package for this socket.


613  Socket 3 limit name Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
xAX string
String



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
12
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: String up to 12 characters (8 bit) that provide a unique name for the socket. All sockets in a burner control must have different names. When a safety packet is received from the module identified by the "Socket N limit module number" register, and when this packet is correct as defined by the SLATE "SafetyDataPackets" document, and when the name provided by this parameter matches the name provided in the packet, then the status data provided by the limit block is used as valid data. A safety packet having a name which does not match any of the sockets (and also the socket's module number) is ignored.


614  Socket 3 limit response Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Response to valid (as defined by other socket configuration registers) limit block status values. The responses below are suppressed during those states when it is not desired, as specified by the value of the "Socket N limit respond when" parameter.

If the response is set to "Recycle 1", "Recycle 2", or "Recycle 3" then, whenever the limit block status is not "Limit OK" then a recycle and hold occurs until the status reverts to "Limit OK"

If the response is set to "Soft lockout" or "Hard lockout" then, whenever the limit block status is not "Limit OK" then the appropriate type of lockout occurs.

If the response is set to "Auto-ignition active" then whenever the limit block status is "Auto ignition threshold exceeded" then the BC, when configured for auto-ignition detection, will act as defined by the "Auto ignition enable" parameter. For this response, the "Socket N response when" parameter value is ignored.

If the "Auto ignition threshold exceeded" status is received but this parameter is not configured for "Auto-ignition active" then this status is ignored.
1 Unknown It is not specified what should happen for an invalid limit event.
2 Recycle 1 Invalid limit event should cause a type 1 recycle to occur.
3 Recycle 2 Invalid limit event should cause a type 2 recycle to occur.
4 Recycle 3 Invalid limit event should cause a type 3 recycle to occur.
5 Soft lockout Invalid limit event should cause a soft lockout to occur.
6 Hard lockout Invalid limit event should cause a hard lockout to occur.
7 Auto-ignition active Operate according to auto-ignition conditions having been met.


615  Socket 3 limit response trigger Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: When the burner control responds to the limit. It also provides a master-disable for the socket. The values are:
Disable - this limit socket is inactive
Always - this limit socket is active without regard to BC state
Prepurge and Ignition and Run - this limit socket is active during the named states (and their substates)
Ignition and Run - this limit socket is active during the named states (and their substates)
Flame is on - this limit socket is active whenever flame is required to be on
Run - this limit socket is active during the BC's Run state (and its substates, if any).
1 Disabled - Ignore limit Limit socket is inactive.
2 Always Check limit in all states.
3 Prepurge, Ignition and Run Only check limit when in prepurge, ignition, or Run states.
4 Ignition and Run Only check limit when in ignition or Run states.
5 Flame is on Only check limit when flame is present.
6 Run Only check limit when in Run state.


618  Socket 4 limit module number Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
U16



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Module number of the Limit module that is providing data for socket "N". No other Limit module will be examined for a safety package for this socket.


619  Socket 4 limit name Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
xAX string
String



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
12
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: String up to 12 characters (8 bit) that provide a unique name for the socket. All sockets in a burner control must have different names. When a safety packet is received from the module identified by the "Socket N limit module number" register, and when this packet is correct as defined by the SLATE "SafetyDataPackets" document, and when the name provided by this parameter matches the name provided in the packet, then the status data provided by the limit block is used as valid data. A safety packet having a name which does not match any of the sockets (and also the socket's module number) is ignored.


620  Socket 4 limit response Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Response to valid (as defined by other socket configuration registers) limit block status values. The responses below are suppressed during those states when it is not desired, as specified by the value of the "Socket N limit respond when" parameter.

If the response is set to "Recycle 1", "Recycle 2", or "Recycle 3" then, whenever the limit block status is not "Limit OK" then a recycle and hold occurs until the status reverts to "Limit OK"

If the response is set to "Soft lockout" or "Hard lockout" then, whenever the limit block status is not "Limit OK" then the appropriate type of lockout occurs.

If the response is set to "Auto-ignition active" then whenever the limit block status is "Auto ignition threshold exceeded" then the BC, when configured for auto-ignition detection, will act as defined by the "Auto ignition enable" parameter. For this response, the "Socket N response when" parameter value is ignored.

If the "Auto ignition threshold exceeded" status is received but this parameter is not configured for "Auto-ignition active" then this status is ignored.
1 Unknown It is not specified what should happen for an invalid limit event.
2 Recycle 1 Invalid limit event should cause a type 1 recycle to occur.
3 Recycle 2 Invalid limit event should cause a type 2 recycle to occur.
4 Recycle 3 Invalid limit event should cause a type 3 recycle to occur.
5 Soft lockout Invalid limit event should cause a soft lockout to occur.
6 Hard lockout Invalid limit event should cause a hard lockout to occur.
7 Auto-ignition active Operate according to auto-ignition conditions having been met.


621  Socket 4 limit response trigger Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: When the burner control responds to the limit. It also provides a master-disable for the socket. The values are:
Disable - this limit socket is inactive
Always - this limit socket is active without regard to BC state
Prepurge and Ignition and Run - this limit socket is active during the named states (and their substates)
Ignition and Run - this limit socket is active during the named states (and their substates)
Flame is on - this limit socket is active whenever flame is required to be on
Run - this limit socket is active during the BC's Run state (and its substates, if any).
1 Disabled - Ignore limit Limit socket is inactive.
2 Always Check limit in all states.
3 Prepurge, Ignition and Run Only check limit when in prepurge, ignition, or Run states.
4 Ignition and Run Only check limit when in ignition or Run states.
5 Flame is on Only check limit when flame is present.
6 Run Only check limit when in Run state.


624  Socket 5 limit module number Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
U16



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Module number of the Limit module that is providing data for socket "N". No other Limit module will be examined for a safety package for this socket.


625  Socket 5 limit name Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
xAX string
String



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
12
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: String up to 12 characters (8 bit) that provide a unique name for the socket. All sockets in a burner control must have different names. When a safety packet is received from the module identified by the "Socket N limit module number" register, and when this packet is correct as defined by the SLATE "SafetyDataPackets" document, and when the name provided by this parameter matches the name provided in the packet, then the status data provided by the limit block is used as valid data. A safety packet having a name which does not match any of the sockets (and also the socket's module number) is ignored.


626  Socket 5 limit response Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Response to valid (as defined by other socket configuration registers) limit block status values. The responses below are suppressed during those states when it is not desired, as specified by the value of the "Socket N limit respond when" parameter.

If the response is set to "Recycle 1", "Recycle 2", or "Recycle 3" then, whenever the limit block status is not "Limit OK" then a recycle and hold occurs until the status reverts to "Limit OK"

If the response is set to "Soft lockout" or "Hard lockout" then, whenever the limit block status is not "Limit OK" then the appropriate type of lockout occurs.

If the response is set to "Auto-ignition active" then whenever the limit block status is "Auto ignition threshold exceeded" then the BC, when configured for auto-ignition detection, will act as defined by the "Auto ignition enable" parameter. For this response, the "Socket N response when" parameter value is ignored.

If the "Auto ignition threshold exceeded" status is received but this parameter is not configured for "Auto-ignition active" then this status is ignored.
1 Unknown It is not specified what should happen for an invalid limit event.
2 Recycle 1 Invalid limit event should cause a type 1 recycle to occur.
3 Recycle 2 Invalid limit event should cause a type 2 recycle to occur.
4 Recycle 3 Invalid limit event should cause a type 3 recycle to occur.
5 Soft lockout Invalid limit event should cause a soft lockout to occur.
6 Hard lockout Invalid limit event should cause a hard lockout to occur.
7 Auto-ignition active Operate according to auto-ignition conditions having been met.


627  Socket 5 limit response trigger Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: When the burner control responds to the limit. It also provides a master-disable for the socket. The values are:
Disable - this limit socket is inactive
Always - this limit socket is active without regard to BC state
Prepurge and Ignition and Run - this limit socket is active during the named states (and their substates)
Ignition and Run - this limit socket is active during the named states (and their substates)
Flame is on - this limit socket is active whenever flame is required to be on
Run - this limit socket is active during the BC's Run state (and its substates, if any).
1 Disabled - Ignore limit Limit socket is inactive.
2 Always Check limit in all states.
3 Prepurge, Ignition and Run Only check limit when in prepurge, ignition, or Run states.
4 Ignition and Run Only check limit when in ignition or Run states.
5 Flame is on Only check limit when flame is present.
6 Run Only check limit when in Run state.


630  Socket 6 limit module number Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
U16



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Module number of the Limit module that is providing data for socket "N". No other Limit module will be examined for a safety package for this socket.


631  Socket 6 limit name Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
xAX string
String



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
12
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: String up to 12 characters (8 bit) that provide a unique name for the socket. All sockets in a burner control must have different names. When a safety packet is received from the module identified by the "Socket N limit module number" register, and when this packet is correct as defined by the SLATE "SafetyDataPackets" document, and when the name provided by this parameter matches the name provided in the packet, then the status data provided by the limit block is used as valid data. A safety packet having a name which does not match any of the sockets (and also the socket's module number) is ignored.


632  Socket 6 limit response Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Response to valid (as defined by other socket configuration registers) limit block status values. The responses below are suppressed during those states when it is not desired, as specified by the value of the "Socket N limit respond when" parameter.

If the response is set to "Recycle 1", "Recycle 2", or "Recycle 3" then, whenever the limit block status is not "Limit OK" then a recycle and hold occurs until the status reverts to "Limit OK"

If the response is set to "Soft lockout" or "Hard lockout" then, whenever the limit block status is not "Limit OK" then the appropriate type of lockout occurs.

If the response is set to "Auto-ignition active" then whenever the limit block status is "Auto ignition threshold exceeded" then the BC, when configured for auto-ignition detection, will act as defined by the "Auto ignition enable" parameter. For this response, the "Socket N response when" parameter value is ignored.

If the "Auto ignition threshold exceeded" status is received but this parameter is not configured for "Auto-ignition active" then this status is ignored.
1 Unknown It is not specified what should happen for an invalid limit event.
2 Recycle 1 Invalid limit event should cause a type 1 recycle to occur.
3 Recycle 2 Invalid limit event should cause a type 2 recycle to occur.
4 Recycle 3 Invalid limit event should cause a type 3 recycle to occur.
5 Soft lockout Invalid limit event should cause a soft lockout to occur.
6 Hard lockout Invalid limit event should cause a hard lockout to occur.
7 Auto-ignition active Operate according to auto-ignition conditions having been met.


633  Socket 6 limit response trigger Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: When the burner control responds to the limit. It also provides a master-disable for the socket. The values are:
Disable - this limit socket is inactive
Always - this limit socket is active without regard to BC state
Prepurge and Ignition and Run - this limit socket is active during the named states (and their substates)
Ignition and Run - this limit socket is active during the named states (and their substates)
Flame is on - this limit socket is active whenever flame is required to be on
Run - this limit socket is active during the BC's Run state (and its substates, if any).
1 Disabled - Ignore limit Limit socket is inactive.
2 Always Check limit in all states.
3 Prepurge, Ignition and Run Only check limit when in prepurge, ignition, or Run states.
4 Ignition and Run Only check limit when in ignition or Run states.
5 Flame is on Only check limit when flame is present.
6 Run Only check limit when in Run state.


636  Socket 7 limit module number Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
U16



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Module number of the Limit module that is providing data for socket "N". No other Limit module will be examined for a safety package for this socket.


637  Socket 7 limit name Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
xAX string
String



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
12
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: String up to 12 characters (8 bit) that provide a unique name for the socket. All sockets in a burner control must have different names. When a safety packet is received from the module identified by the "Socket N limit module number" register, and when this packet is correct as defined by the SLATE "SafetyDataPackets" document, and when the name provided by this parameter matches the name provided in the packet, then the status data provided by the limit block is used as valid data. A safety packet having a name which does not match any of the sockets (and also the socket's module number) is ignored.


638  Socket 7 limit response Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Response to valid (as defined by other socket configuration registers) limit block status values. The responses below are suppressed during those states when it is not desired, as specified by the value of the "Socket N limit respond when" parameter.

If the response is set to "Recycle 1", "Recycle 2", or "Recycle 3" then, whenever the limit block status is not "Limit OK" then a recycle and hold occurs until the status reverts to "Limit OK"

If the response is set to "Soft lockout" or "Hard lockout" then, whenever the limit block status is not "Limit OK" then the appropriate type of lockout occurs.

If the response is set to "Auto-ignition active" then whenever the limit block status is "Auto ignition threshold exceeded" then the BC, when configured for auto-ignition detection, will act as defined by the "Auto ignition enable" parameter. For this response, the "Socket N response when" parameter value is ignored.

If the "Auto ignition threshold exceeded" status is received but this parameter is not configured for "Auto-ignition active" then this status is ignored.
1 Unknown It is not specified what should happen for an invalid limit event.
2 Recycle 1 Invalid limit event should cause a type 1 recycle to occur.
3 Recycle 2 Invalid limit event should cause a type 2 recycle to occur.
4 Recycle 3 Invalid limit event should cause a type 3 recycle to occur.
5 Soft lockout Invalid limit event should cause a soft lockout to occur.
6 Hard lockout Invalid limit event should cause a hard lockout to occur.
7 Auto-ignition active Operate according to auto-ignition conditions having been met.


639  Socket 7 limit response trigger Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: When the burner control responds to the limit. It also provides a master-disable for the socket. The values are:
Disable - this limit socket is inactive
Always - this limit socket is active without regard to BC state
Prepurge and Ignition and Run - this limit socket is active during the named states (and their substates)
Ignition and Run - this limit socket is active during the named states (and their substates)
Flame is on - this limit socket is active whenever flame is required to be on
Run - this limit socket is active during the BC's Run state (and its substates, if any).
1 Disabled - Ignore limit Limit socket is inactive.
2 Always Check limit in all states.
3 Prepurge, Ignition and Run Only check limit when in prepurge, ignition, or Run states.
4 Ignition and Run Only check limit when in ignition or Run states.
5 Flame is on Only check limit when flame is present.
6 Run Only check limit when in Run state.


642  Socket 8 limit module number Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
U16



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Module number of the Limit module that is providing data for socket "N". No other Limit module will be examined for a safety package for this socket.


643  Socket 8 limit name Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
xAX string
String



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
12
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: String up to 12 characters (8 bit) that provide a unique name for the socket. All sockets in a burner control must have different names. When a safety packet is received from the module identified by the "Socket N limit module number" register, and when this packet is correct as defined by the SLATE "SafetyDataPackets" document, and when the name provided by this parameter matches the name provided in the packet, then the status data provided by the limit block is used as valid data. A safety packet having a name which does not match any of the sockets (and also the socket's module number) is ignored.


644  Socket 8 limit response Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: Response to valid (as defined by other socket configuration registers) limit block status values. The responses below are suppressed during those states when it is not desired, as specified by the value of the "Socket N limit respond when" parameter.

If the response is set to "Recycle 1", "Recycle 2", or "Recycle 3" then, whenever the limit block status is not "Limit OK" then a recycle and hold occurs until the status reverts to "Limit OK"

If the response is set to "Soft lockout" or "Hard lockout" then, whenever the limit block status is not "Limit OK" then the appropriate type of lockout occurs.

If the response is set to "Auto-ignition active" then whenever the limit block status is "Auto ignition threshold exceeded" then the BC, when configured for auto-ignition detection, will act as defined by the "Auto ignition enable" parameter. For this response, the "Socket N response when" parameter value is ignored.

If the "Auto ignition threshold exceeded" status is received but this parameter is not configured for "Auto-ignition active" then this status is ignored.
1 Unknown It is not specified what should happen for an invalid limit event.
2 Recycle 1 Invalid limit event should cause a type 1 recycle to occur.
3 Recycle 2 Invalid limit event should cause a type 2 recycle to occur.
4 Recycle 3 Invalid limit event should cause a type 3 recycle to occur.
5 Soft lockout Invalid limit event should cause a soft lockout to occur.
6 Hard lockout Invalid limit event should cause a hard lockout to occur.
7 Auto-ignition active Operate according to auto-ignition conditions having been met.


645  Socket 8 limit response trigger Category: Limit Socket
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle

1

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description: When the burner control responds to the limit. It also provides a master-disable for the socket. The values are:
Disable - this limit socket is inactive
Always - this limit socket is active without regard to BC state
Prepurge and Ignition and Run - this limit socket is active during the named states (and their substates)
Ignition and Run - this limit socket is active during the named states (and their substates)
Flame is on - this limit socket is active whenever flame is required to be on
Run - this limit socket is active during the BC's Run state (and its substates, if any).
1 Disabled - Ignore limit Limit socket is inactive.
2 Always Check limit in all states.
3 Prepurge, Ignition and Run Only check limit when in prepurge, ignition, or Run states.
4 Ignition and Run Only check limit when in ignition or Run states.
5 Flame is on Only check limit when flame is present.
6 Run Only check limit when in Run state.


648  Flame amplifier 1 required type Category: Flame Module Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description:
1 None None means this is unused or setup is needed
2 UV Ampli-Check Ultraviolet Minipeeper detector (C7027 / C7035)
3 UV Shutter-Check Ultraviolet Purple Peeper detector (C7061) with shutter
4 IR Ampli-Check Infrared (Lead sulfide) detector (C7915)
5 UV/Visible Ampli-Check Ultraviolet (C7927) or Visible light (C7962) solid state detector
6 Rectification Ampli-Check Flame rod (C7000x) or UV solid state Purple peeper (C7012 A/C) detector with shutter.


649  Flame amplifier 1 flame threshold Category: Flame Module Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-float
F32

0.8

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
4
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description:


650  Flame amplifier 1 weak flame threshold Category: Flame Module Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-float
F32

1.2

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
4
Yes
Yes - Configuration data
No
Yes - Can set up in AX
  Description:


655  Flame amplifier 2 required type Category: Flame Module Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description:
1 None None means this is unused or setup is needed
2 UV Ampli-Check Ultraviolet Minipeeper detector (C7027 / C7035)
3 UV Shutter-Check Ultraviolet Purple Peeper detector (C7061) with shutter
4 IR Ampli-Check Infrared (Lead sulfide) detector (C7915)
5 UV/Visible Ampli-Check Ultraviolet (C7927) or Visible light (C7962) solid state detector
6 Rectification Ampli-Check Flame rod (C7000x) or UV solid state Purple peeper (C7012 A/C) detector with shutter.


656  Flame amplifier 2 flame threshold Category: Flame Module Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-float
F32

0.8

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
4
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description:


657  Flame amplifier 2 weak flame threshold Category: Flame Module Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-float
F32

1.2

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
4
Yes
Yes - Configuration data
No
Yes - Can set up in AX
  Description:


662  Flame amplifier 3 required type Category: Flame Module Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description:
1 None None means this is unused or setup is needed
2 UV Ampli-Check Ultraviolet Minipeeper detector (C7027 / C7035)
3 UV Shutter-Check Ultraviolet Purple Peeper detector (C7061) with shutter
4 IR Ampli-Check Infrared (Lead sulfide) detector (C7915)
5 UV/Visible Ampli-Check Ultraviolet (C7927) or Visible light (C7962) solid state detector
6 Rectification Ampli-Check Flame rod (C7000x) or UV solid state Purple peeper (C7012 A/C) detector with shutter.


663  Flame amplifier 3 flame threshold Category: Flame Module Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-float
F32

0.8

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
4
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description:


664  Flame amplifier 3 weak flame threshold Category: Flame Module Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-float
F32

1.2

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
4
Yes
Yes - Configuration data
No
Yes - Can set up in AX
  Description:


669  Flame amplifier 4 required type Category: Flame Module Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-uint16
EnumSingle



Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
2
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description:
1 None None means this is unused or setup is needed
2 UV Ampli-Check Ultraviolet Minipeeper detector (C7027 / C7035)
3 UV Shutter-Check Ultraviolet Purple Peeper detector (C7061) with shutter
4 IR Ampli-Check Infrared (Lead sulfide) detector (C7915)
5 UV/Visible Ampli-Check Ultraviolet (C7927) or Visible light (C7962) solid state detector
6 Rectification Ampli-Check Flame rod (C7000x) or UV solid state Purple peeper (C7012 A/C) detector with shutter.


670  Flame amplifier 4 flame threshold Category: Flame Module Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-float
F32

0.8

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
4
Yes
Yes - Configuration data
Yes - Safety data
Yes - Can set up in AX
  Description:


671  Flame amplifier 4 weak flame threshold Category: Flame Module Setup
  Units;
DataType:
Max:
Default Value:
Min:
VAL-float
F32

1.2

Units Code:
Size:
Writable:
Permanent:
Verified:
DesignSetup:
256
4
Yes
Yes - Configuration data
No
Yes - Can set up in AX
  Description: